          PRODUCT OVERVIEW

          NYKW2 series intelligent universal circuit breakers are mainly used to distribute electric energy and protect lines and power supply equipment from overload, undervoltage, short circuit, single-phase grounding and other faults. It adopts intelligent control unit with various protection modes to improve the reliability of power supply. It also has open communication interface for four remote control functions to meet the requirements of the control center and automation system.

          NYKW2 series intelligent universal circuit breaker complies with GB14048.2 "Low-voltage Switchgear and Controgear—Circuit-breakers" and IEC60947-2 "Low-voltage Switchgear and Controlgear—Circuit-breakers" and other standards.

          ZERO ARC

          Adopts magnetic blowing arc extinguishing technology and multi-layer metal grating structure for arc extinguishing, and gratings are staggeredly arranged in "V" groove, which can effectively improve the arc voltage. Also, the side walls of the arc extinguishing chamber are made of gas-producing materials, which can increase the air pressure in the chamber and facilitate the arc into the arc extinguishing chamber to rapidly extinguish the arc, so that it becomes a zero-arc air circuit breaker.

          HIGH BREAKING CAPACITY

          Adopts dual structure of main and arc contacts, and the rated current is borne by the main contact, and the arc is borne by the arc contact, thus the burning damage caused by the arc to the main contact is very small.

          Designed with new contact support, the electrodynamic repulsion force compensates for contact pressure, so that it has better dynamic and thermal stability. The gas-producing material wraps the movable and static contacts, and the high-pressure gas drives the arc to flow to the arc extinguishing chamber quickly, extending the service life of the contacts.
          The main contact is comb-shaped and composed of a number of contacts in parallel to reduce the electrodynamic repulsion force and improve the heat dissipation effect, which is conducive to the improvement of product performance indicators (reliability, temperature rise, breaking capacity, etc.).

          INTELLIGENCE

          Relying on various sensor technologies, microelectronic technologies and various information transmission technologies, NYKW2 series intelligent circuit breakers integrate the functions of control, measurement and communication, which can better break and protect the circuit. It has a variety of protection functions suitable for different application scenarios in order to meet the requirements of control centers and automation systems, and realize the intelligent operation of circuit breakers.

          ABUNDANT EXPANSION SPACE

          Programmable relay signaling units, zone selective interlocking (ZSI), load monitoring, demand value measurement and other expansion units are available to meet the needs of different applications.

          Technical Parameters

          BASIC TECHNICAL PARAMETERS

          Model Rated operating voltage Ue(V) Rated insulation voltage Ui(V) 50Hz Rated impulse withstand voltage Uimp(V) Casing current Inm(A) Rated currentIn(A) Number of poles Short-circuit breaking capacity Rated short-circuit making capacity Icm(kA) (peak) Rated short-time withstand current Icw(kA)/1s N-phase rated current In(A)
          Rated ultimate short-circuit breaking capacity Icu(kA) Rated operating short-circuit breaking capacity Ics(kA)
          AC400V AC690V AC400V AC690V AC
          400V
          AC
          690V
          AC
          400V
          AC
          690V
          NYKW2-2000 AC400、690 AC1000 AC12000 2000 630 3、4 85 50 65 40 187 105 65 40 100%In
          800 85 50 65 40 187 105 65 40
          1000 85 50 65 40 187 105 65 40
          1250 85 50 65 40 187 105 65 40
          1600 85 50 65 40 187 105 65 40
          2000 85 50 65 40 187 105 65 40
          NYKW2-3200 3200 2000 100 65 65 50 220 143 65 50
          2500 100 65 65 50 220 143 65 50
          2900 100 65 65 50 220 143 65 50
          3200 100 65 65 50 220 143 65 50
          NYKW2-4000 4000 3600 120 85 100 80 264 187 100 80 50%In
          3600 120 85 100 80 264 187 100 80
          NYKW2-6300 6300 4000 120 80 100 65 264 165 100 65
          5000 120 80 100 65 264 165 100 65
          6300 120 80 100 65 264 165 100 65

          NYKW2 Series Controller Catalog

          Controller Model NT-2L NT-M NT-2M NT-3M NT-2H NT-3H
          Display mode Electronic display Digital display Digital display LCD display Digital display LCD display
          Overload long delay protection
          Short-circuit short delay protection
          Short-circuit instantaneous protection
          Grounding fault protection
          Current imbalance protection - -
          Functional test
          Fault memory
          Signal contact output
          Thermal memory
          Self-diagnostics
          MCU operating indication - - - - -
          Current columnar display - - - - -
          Current measurement -
          MCR and override tripping
          Load monitoring -
          Fault status indication and value display
          Voltage measurement -
          Power factor - -
          Power measurement - -
          Electrical energy measurement - -
          Communication function - - - -
          Contact wear indication function - -
          Zone selective interlocking - - - -
          Harmonic measurement - - - -
          Voltage protection - - - -
          Memory of grid history parameters - -
          Counting function - -

          Description: ●   Standard function    〇  Optional function     -  Not supported

          Selection table

          NYKW2 2000 3P 630A Model M Drawer type horizontal wiring Additional functions
          Product code Casing grade Pole No. Rated current Intelligent controller Installation method Additional functions
          NYKW2:
          Intelligent universal circuit
          breaker
          2000A
          3200A
          4000A
          6300A
          3P:3 pole
          4P:4 pole
          630A
          800A
          1000A
          1250A
          1600A
          2000A
          2500A
          2900A
          3200A
          3600A
          4000A
          5000A
          6300A
          2L type
          M type
          2M type
          3M type
          2H type
          3H type
          Fixed horizontal wiring
          Drawer type horizontal wiring
          Fixed vertical wiring
          Drawer type vertical wiring
          Under-voltage tripper
          No-voltage tripper
          External current transformer (3P+N)
          One lock and one key
          Two locks and one key
          Three locks and two keys
          Steel cable type mechanical interlocking
          Technical Parameters

          Basic technical parameters

          • Rated operating voltage Ue(V) :AC400、690

            Rated insulation voltage Ui(V) 50Hz:AC1000

            Rated impulse withstand voltage Uimp(V):AC12000

            Casing current Inm(A) :2000

            Rated currentIn(A):630

            Number of poles :3、4

            Rated ultimate short-circuit breaking capacity Icu(kA) :85(AC400V);50(AC690V)

            Rated operating short-circuit breaking capacity Ics(kA) :65(AC400V);40(AC690V)

            Rated short-circuit making capacity Icm(kA) (peak) :187(AC400V);105(AC690V)

            Rated short-time withstand current Icw(kA)/1s :65(AC400V);40(AC690V)

            N-phase rated current In(A):100%In

          • Rated operating voltage Ue(V) :AC400、690

            Rated insulation voltage Ui(V) 50Hz:AC1000

            Rated impulse withstand voltage Uimp(V):AC12000

            Casing current Inm(A) :2000

            Rated currentIn(A):800

            Number of poles :3、4

            Rated ultimate short-circuit breaking capacity Icu(kA) :85(AC400V);50(AC690V)

            Rated operating short-circuit breaking capacity Ics(kA) :65(AC400V);40(AC690V)

            Rated short-circuit making capacity Icm(kA) (peak) :187(AC400V);105(AC690V)

            Rated short-time withstand current Icw(kA)/1s :65(AC400V);40(AC690V)

            N-phase rated current In(A):100%In

          • Rated operating voltage Ue(V) :AC400、690

            Rated insulation voltage Ui(V) 50Hz:AC1000

            Rated impulse withstand voltage Uimp(V):AC12000

            Casing current Inm(A) :2000

            Rated currentIn(A):1000

            Number of poles :3、4

            Rated ultimate short-circuit breaking capacity Icu(kA) :85(AC400V);50(AC690V)

            Rated operating short-circuit breaking capacity Ics(kA) :65(AC400V);40(AC690V)

            Rated short-circuit making capacity Icm(kA) (peak) :187(AC400V);105(AC690V)

            Rated short-time withstand current Icw(kA)/1s :65(AC400V);40(AC690V)

            N-phase rated current In(A):100%In

          • Rated operating voltage Ue(V) :AC400、690

            Rated insulation voltage Ui(V) 50Hz:AC1000

            Rated impulse withstand voltage Uimp(V):AC12000

            Casing current Inm(A) :2000

            Rated currentIn(A):1250

            Number of poles :3、4

            Rated ultimate short-circuit breaking capacity Icu(kA) :85(AC400V);50(AC690V)

            Rated operating short-circuit breaking capacity Ics(kA) :65(AC400V);40(AC690V)

            Rated short-circuit making capacity Icm(kA) (peak) :187(AC400V);105(AC690V)

            Rated short-time withstand current Icw(kA)/1s :65(AC400V);40(AC690V)

            N-phase rated current In(A):100%In

          • Rated operating voltage Ue(V) :AC400、690

            Rated insulation voltage Ui(V) 50Hz:AC1000

            Rated impulse withstand voltage Uimp(V):AC12000

            Casing current Inm(A) :2000

            Rated currentIn(A):1600

            Number of poles :3、4

            Rated ultimate short-circuit breaking capacity Icu(kA) :85(AC400V);50(AC690V)

            Rated operating short-circuit breaking capacity Ics(kA) :65(AC400V);40(AC690V)

            Rated short-circuit making capacity Icm(kA) (peak) :187(AC400V);105(AC690V)

            Rated short-time withstand current Icw(kA)/1s :65(AC400V);40(AC690V)

            N-phase rated current In(A):100%In

          • Rated operating voltage Ue(V) :AC400、690

            Rated insulation voltage Ui(V) 50Hz:AC1000

            Rated impulse withstand voltage Uimp(V):AC12000

            Casing current Inm(A) :2000

            Rated currentIn(A):2000

            Number of poles :3、4

            Rated ultimate short-circuit breaking capacity Icu(kA) :85(AC400V);50(AC690V)

            Rated operating short-circuit breaking capacity Ics(kA) :65(AC400V);40(AC690V)

            Rated short-circuit making capacity Icm(kA) (peak) :187(AC400V);105(AC690V)

            Rated short-time withstand current Icw(kA)/1s :65(AC400V);40(AC690V)

            N-phase rated current In(A):100%In

          • Rated operating voltage Ue(V) :AC400、690

            Rated insulation voltage Ui(V) 50Hz:AC1000

            Rated impulse withstand voltage Uimp(V):AC12000

            Casing current Inm(A) :3200

            Rated currentIn(A):2000

            Number of poles :3、4

            Rated ultimate short-circuit breaking capacity Icu(kA) :100(AC400V);65(AC690V)

            Rated operating short-circuit breaking capacity Ics(kA) :65(AC400V);50(AC690V)

            Rated short-circuit making capacity Icm(kA) (peak) :220(AC400V);143(AC690V)

            Rated short-time withstand current Icw(kA)/1s :65(AC400V);50(AC690V)

            N-phase rated current In(A):100%In

          • Rated operating voltage Ue(V) :AC400、690

            Rated insulation voltage Ui(V) 50Hz:AC1000

            Rated impulse withstand voltage Uimp(V):AC12000

            Casing current Inm(A) :3200

            Rated currentIn(A):2500

            Number of poles :3、4

            Rated ultimate short-circuit breaking capacity Icu(kA) :100(AC400V);65(AC690V)

            Rated operating short-circuit breaking capacity Ics(kA) :65(AC400V);50(AC690V)

            Rated short-circuit making capacity Icm(kA) (peak) :220(AC400V);143(AC690V)

            Rated short-time withstand current Icw(kA)/1s :65(AC400V);50(AC690V)

            N-phase rated current In(A):100%In

          • Rated operating voltage Ue(V) :AC400、690

            Rated insulation voltage Ui(V) 50Hz:AC1000

            Rated impulse withstand voltage Uimp(V):AC12000

            Casing current Inm(A) :3200

            Rated currentIn(A):2900

            Number of poles :3、4

            Rated ultimate short-circuit breaking capacity Icu(kA) :100(AC400V);65(AC690V)

            Rated operating short-circuit breaking capacity Ics(kA) :65(AC400V);50(AC690V)

            Rated short-circuit making capacity Icm(kA) (peak) :220(AC400V);143(AC690V)

            Rated short-time withstand current Icw(kA)/1s :65(AC400V);50(AC690V)

            N-phase rated current In(A):100%In

          • Rated operating voltage Ue(V) :AC400、690

            Rated insulation voltage Ui(V) 50Hz:AC1000

            Rated impulse withstand voltage Uimp(V):AC12000

            Casing current Inm(A) :3200

            Rated currentIn(A):3200

            Number of poles :3、4

            Rated ultimate short-circuit breaking capacity Icu(kA) :100(AC400V);65(AC690V)

            Rated operating short-circuit breaking capacity Ics(kA) :65(AC400V);50(AC690V)

            Rated short-circuit making capacity Icm(kA) (peak) :220(AC400V);143(AC690V)

            Rated short-time withstand current Icw(kA)/1s :65(AC400V);50(AC690V)

            N-phase rated current In(A):100%In

          • Rated operating voltage Ue(V) :AC400、690

            Rated insulation voltage Ui(V) 50Hz:AC1000

            Rated impulse withstand voltage Uimp(V):AC12000

            Casing current Inm(A) :4000

            Rated currentIn(A):3600

            Number of poles :3、4

            Rated ultimate short-circuit breaking capacity Icu(kA) :120(AC400V);85(AC690V)

            Rated operating short-circuit breaking capacity Ics(kA) :100(AC400V);80(AC690V)

            Rated short-circuit making capacity Icm(kA) (peak) :264(AC400V);187(AC690V)

            Rated short-time withstand current Icw(kA)/1s :100(AC400V);80(AC690V)

            N-phase rated current In(A):100%In

          • Rated operating voltage Ue(V) :AC400、690

            Rated insulation voltage Ui(V) 50Hz:AC1000

            Rated impulse withstand voltage Uimp(V):AC12000

            Casing current Inm(A) :4000

            Rated currentIn(A):4000

            Number of poles :3、4

            Rated ultimate short-circuit breaking capacity Icu(kA) :120(AC400V);85(AC690V)

            Rated operating short-circuit breaking capacity Ics(kA) :100(AC400V);80(AC690V)

            Rated short-circuit making capacity Icm(kA) (peak) :264(AC400V);187(AC690V)

            Rated short-time withstand current Icw(kA)/1s :100(AC400V);80(AC690V)

            N-phase rated current In(A):100%In

          • Rated operating voltage Ue(V) :AC400、690

            Rated insulation voltage Ui(V) 50Hz:AC1000

            Rated impulse withstand voltage Uimp(V):AC12000

            Casing current Inm(A) :6300

            Rated currentIn(A):4000

            Number of poles :3、4

            Rated ultimate short-circuit breaking capacity Icu(kA) :120(AC400V);80(AC690V)

            Rated operating short-circuit breaking capacity Ics(kA) :100(AC400V);65(AC690V)

            Rated short-circuit making capacity Icm(kA) (peak) :264(AC400V);165(AC690V)

            Rated short-time withstand current Icw(kA)/1s :100(AC400V);65(AC690V)

            N-phase rated current In(A):100%In

          • Rated operating voltage Ue(V) :AC400、690

            Rated insulation voltage Ui(V) 50Hz:AC1000

            Rated impulse withstand voltage Uimp(V):AC12000

            Casing current Inm(A) :6300

            Rated currentIn(A):5000

            Number of poles :3、4

            Rated ultimate short-circuit breaking capacity Icu(kA) :120(AC400V);80(AC690V)

            Rated operating short-circuit breaking capacity Ics(kA) :100(AC400V);65(AC690V)

            Rated short-circuit making capacity Icm(kA) (peak) :264(AC400V);165(AC690V)

            Rated short-time withstand current Icw(kA)/1s :100(AC400V);65(AC690V)

            N-phase rated current In(A):100%In

          • Rated operating voltage Ue(V) :AC400、690

            Rated insulation voltage Ui(V) 50Hz:AC1000

            Rated impulse withstand voltage Uimp(V):AC12000

            Casing current Inm(A) :6300

            Rated currentIn(A):6300

            Number of poles :3、4

            Rated ultimate short-circuit breaking capacity Icu(kA) :120(AC400V);80(AC690V)

            Rated operating short-circuit breaking capacity Ics(kA) :100(AC400V);65(AC690V)

            Rated short-circuit making capacity Icm(kA) (peak) :264(AC400V);165(AC690V)

            Rated short-time withstand current Icw(kA)/1s :100(AC400V);65(AC690V)

            N-phase rated current In(A):100%In

          NYKW2 Series Controller Catalog

          • Display mode:Electronic display

            Overload long delay protection:●

            Short-circuit short delay protection:〇

            Short-circuit instantaneous protection:●

            Grounding fault protection:〇

            Current imbalance protection:-

            Functional test:●

            Fault memory:●

            Signal contact output:〇

            Thermal memory:●

            Self-diagnostics:●

            MCU operating indication:●

            Current columnar display:●

            Current measurement:-

            MCR and override tripping:〇

            Load monitoring:-

            Fault status indication and value display:●

            Voltage measurement:-

            Power factor :-

            Power measurement:-

            Electrical energy measurement:-

            Electrical energy measurement:-

            Communication function:-

            Contact wear indication function:-

            Zone selective interlocking:-

            Harmonic measurement:-

            Voltage protection:-

            Memory of grid history parameters:-

            Counting function:-

          • Display mode:Digital display

            Overload long delay protection:●

            Short-circuit short delay protection:●

            Short-circuit instantaneous protection:●

            Grounding fault protection:●

            Current imbalance protection:-

            Functional test:●

            Fault memory:●

            Signal contact output:〇

            Thermal memory:●

            Self-diagnostics:●

            MCU operating indication:-

            Current columnar display:-

            Current measurement:●

            MCR and override tripping:〇

            Load monitoring:〇

            Fault status indication and value display:●

            Voltage measurement:〇

            Power factor :-

            Power measurement:-

            Electrical energy measurement:-

            Communication function:-

            Contact wear indication function:-

            Zone selective interlocking:-

            Harmonic measurement:-

            Voltage protection:-

            Memory of grid history parameters:-

            Counting function:-

          • Display mode:Digital display

            Overload long delay protection:●

            Short-circuit short delay protection:●

            Short-circuit instantaneous protection:●

            Grounding fault protection:●

            Current imbalance protection:〇

            Functional test:●

            Fault memory:●

            Signal contact output:〇

            Thermal memory:●

            Self-diagnostics:●

            MCU operating indication:-

            Current columnar display:-

            Current measurement:●

            MCR and override tripping:〇

            Load monitoring:〇

            Fault status indication and value display:●

            Voltage measurement:〇

            Power factor :〇

            Power measurement:〇

            Electrical energy measurement:〇

            Communication function:-

            Contact wear indication function:●

            Zone selective interlocking:-

            Harmonic measurement:-

            Voltage protection:-

            Memory of grid history parameters:〇

            Counting function:●

          • Display mode:LCD display

            Overload long delay protection:●

            Short-circuit short delay protection:●

            Short-circuit instantaneous protection:●

            Grounding fault protection:●

            Current imbalance protection:〇

            Functional test:●

            Fault memory:●

            Signal contact output:〇

            Thermal memory:●

            Self-diagnostics:●

            MCU operating indication:-

            Current columnar display:-

            Current measurement:●

            MCR and override tripping:〇

            Load monitoring:〇

            Fault status indication and value display:●

            Voltage measurement:〇

            Power factor :〇

            Power measurement:〇

            Electrical energy measurement:〇

            Communication function:-

            Contact wear indication function:●

            Zone selective interlocking:〇

            Harmonic measurement:〇

            Voltage protection:〇

            Memory of grid history parameters:〇

            Counting function:●

          • Display mode:Digital display

            Overload long delay protection:●

            Short-circuit short delay protection:●

            Short-circuit instantaneous protection:●

            Grounding fault protection:●

            Current imbalance protection:〇

            Functional test:●

            Fault memory:●

            Signal contact output:〇

            Thermal memory:●

            Self-diagnostics:●

            MCU operating indication:-

            Current columnar display:-

            Current measurement:●

            MCR and override tripping:〇

            Load monitoring:〇

            Fault status indication and value display:●

            Voltage measurement:〇

            Power factor :〇

            Power measurement:〇

            Electrical energy measurement:〇

            Communication function:●

            Contact wear indication function:●

            Zone selective interlocking:-

            Harmonic measurement:-

            Voltage protection:-

            Memory of grid history parameters:〇

            Counting function:●

          • Display mode:LCD display

            Overload long delay protection:●

            Short-circuit short delay protection:●

            Short-circuit instantaneous protection:●

            Grounding fault protection:●

            Current imbalance protection:〇

            Functional test:●

            Fault memory:●

            Signal contact output:〇

            Thermal memory:●

            Self-diagnostics:●

            MCU operating indication:-

            Current columnar display:-

            Current measurement:●

            MCR and override tripping:〇

            Load monitoring:〇

            Fault status indication and value display:●

            Voltage measurement:〇

            Power factor :〇

            Power measurement:〇

            Electrical energy measurement:〇

            Communication function:●

            Contact wear indication function:●

            Zone selective interlocking:〇

            Harmonic measurement:〇

            Voltage protection:〇

            Memory of grid history parameters:〇

            Counting function:●

          Description: ●   Standard function    〇  Optional function     -  Not supported

          Selection table


          • Product code :NYKW2: Intelligent universal circuit breaker

            Casing grade:2000A/3200A/4000A/6300A

            Pole No.:3P:3 pole/4P:4 pole

            Rated current:630A/800A/1000A/1250A /1600A/2000A/2500A/2900A/3200A/3600A/4000A/5000A/6300A

            Intelligent controller:2L type/Model M/2Model M/3Model M/2H type /3H type/

            Installation method:Fixed horizontal wiring/Drawer type horizontal wiring/Fixed vertical wiring/Drawer type vertical wiring

            Additional functions:Under-voltage tripper/No-voltage tripper/External current transformer (3P+N)/One lock and one key/Two locks and one key/Three locks and two keys/Steel cable type mechanical interlocking

          page top