          Product Features

          • Tysen-KLD online monitoring technology is used for online monitoring of the mechanical properties of the circuit breaker;
          • Tysen-KLD modular spring operating mechanism technology is used to realize maintenance-free of mechanism;
          • Vacuum interrupter solid-insulation-embedded pole manufactured by joint venture is used to ensure stable quality and excellent performance;
          • The passivation surface treatment process of zinc-cobalt alloy hexavalent chromium in Malaysia shall be introduced, and the level of salt spray resistance test is up to 300 hrs;
          • The German INA customized copper-based high-pressure alloy oil-free bearings are used to achieve self-lubrication of drive mechanism;
          • Mechanical life of 30,000 cycles.

          Structural Characteristics

          • The VPN-12 intelligent vacuum circuit breaker uses Tysen-KLD modular spring operating mechanism, used with JVs's solid-insulation-embedded pole products, of which features are: high dielectric strength, little influence by environmental factors, smaller contact surface areas between conductors, and low loop resistance; at the same time technical advantages and strict quality management system on products of joint venture.
          • The VPN-12 intelligent vacuum circuit breaker is applied with Tysen-KLD online monitoring technology to achieve real-time monitoring on the mechanical properties of the circuit breaker, which gives automatic alarm according to the relevant technical parameters monitored .
          • The product can be used alone, or alternatively incorporated in the mid-set switchgear and fixed switchgear.

          Main Specifications and Technical Parameters

          Main Specifications and Technical Parameters of Circuit Breaker

          No. Description Unit Parameters
          1 Rated voltage kV 12
          2 Rated power frequency withstand voltage (1 min) kV 42/48
          3 Rated lightning impulse/fracture withstand voltage (peak) kV 75/85
          4 Rated frequency Hz 50
          5 Rated current A 630
          1250
          630、1250
          1600、2000、2500
          1250、1600、2000
          2500、3150、4000*
          6 Rated short-circuit breaking current kA 20 25 31.5 40
          7 Rated short-circuit making current kA 50 63 80 100
          8 Rated peak withstand current kA 50 63 80 100
          9 Rated thermal stability current (effective value) kA 20 25 31.5 40
          10 Rated short-circuit duration s 4
          11 Rated operations of short-circuit breaking current Number of cycles 30 30 20
          12 Mechanical life Number of cycles 30000 30000
          13 Rated single/back to back capacitor bank breaking current A 630/400(40kA for 800/400)
          14 Phase-to-phase mm below 1600A:210±1.5
          above 2000A:275±1.5
          15 Allowable wearing accumulation thickness of dynamic and static contacts mm 3
          16 Time interval between opening of first and last phase of three phase circuit-breaker ms ≤ 2
          17 Bouncing time of contactor closed ms ≤2(40kA≤3)
          18 Opening time ms 20-50
          19 Closing time ms 35-70
          20 Rated operating sequence   0.3s 180s
          0——CO——CO
          180s 180s
          0——CO——CO
          21 Actuator corrosion resistance (salt spray test) h 300

          Note: *4000A requires forced air cooling.